ZLCD***1 zinc oxide arrester with electric testing instrument is
dedicated and used to verify electric performance of zinc oxide
arrester,it is suitable for all kinds of voltage level zinc oxide
arrester with and without electric testing, thus detect moisture
inside the device and valve insulation aging and other dangerous
defects.
Instrument is easy to operate and use,microcomputer control the
whole process,can measure zinc oxide arresters full
currentã€resistive current and its harmonic waveã€power frequency
reference voltage and harmonic waveã€active power and phase
difference, big screen can display real waveform of voltage and
current. Instrument is using digital wave analysis
technology,adopts harmonic analysis and digital filtering and so
on software resisting interference method which makes testing
result to be accurateã€stable,can analyze accurately fundamental
wave and 3 ~7 harmonic content,and can overcome the impact of
interference between phases, correctively measure resistive current
of side phase arrester.
Features:
I. **0×**0 color LCD touch
panel, high speed thermal printer; photo and context display and
intuitive interface, it is easy for onsite operation and use.
II. Wireless transmission PT signal
is over **0 meters,if special requirement configuration, can up
to ***0 meters.
III. It is suitable and used for arrester
with powerã€no power and lab room and so on please.
IV. Really do 3 phases current and 3 phases
voltage testing at the same time, improve working efficiency;
Instrument only bring weak power internally, voltage is no more
than *2V; Currentã€voltage sensor is totally quarantined,safe
and firmly.
V. Supports both wire
synchronizationã€wireless sync voltage reference signal
samplingï¼›also supports no voltage method, find voltage reference
by software calculation.
VI. Select equipped high power lithium ion
battery, very helpful for no power place. Instrument only have weak
electric.
VII.Equipped with embedded industrial grade operating
system, support direct shut down method; equipped one USB port,
support U disk export data; can plug external USB mouseã€keyboard
, easy operation.
VIII. Internal equipped 4G capacity SD card
can store big volume data, and have data managementã€storage
function and so on.
IX. Equipped superior management
software,have historical data managementã€data analysisã€report
printing function and so on.
X. High speed sampling
frequency,advanced digital signal process technology,strong
anti-interference ability, super high accuracy of testing
result.
XI. Adopt
dust-proofã€water-proofã€anticorrosion engineering plastic sealed
box,small size,light weight,easy for hand carry.
Parameters:
I. Working
power:**0Vã€*0Hz or internal battery for power
supply.
II. Measurement scope:
Leakage current ***0mA(scalable),
voltage:*****0V(scalable)
III. Measurement accuracy:
Current:full current >**0μA: ±5%
reading 1 bit,
Voltage:reference voltage signal >*0V: ±5% reading±1
bit.
IV. Measurement parameter:
Leakage current full current wave formã€reference wave valid
valueã€peak value.
Leakage current resistive component reference wave valid value and
3ã€5ã€7 times valid value.
Leakage current resistive component peak value:positive peak
value Ir+ negative peak value Ir-.
Capacitive current reference wave,full voltageã€full current and
phase angle difference.
Voltage effective value.
Arrester power lost.
V. Voltage reference signal sampling
method:
Wire sync:*0 meters(scalable)
Wireless sync:>**0
meters(scalable)
VI. Battery parameters:
Charge
time > 6 hours
Continual working time > 4 hours
Interrupted working time > 8 hours
VII.Instrument dimension: host
*6cm×*6cm×*4cm equipped assessor case *2cm×*3cm×*0cm
VIII. Instrument weight: host 5.0kg, equipped
assessor case: 9.0kg